          Central heating boiler heating steam pipeline heat loss analysis and solutions!

          發(fā)布時間:2012-04-25 17:44:24    點擊:1375次

          At present the factory outside the steam line only charge for residents, the baths and hot water heat supply hotels. According to the detection data, found that the steam line heat loss is severe, cause huge waste of energy, increased the enterprise operation and management costs, therefore must be solved as soon as possible.

          - Author: Dushanzi Petrochemical Company - Jiang Kun Wu Yong Xu Chunhua

          1current situation analysis

          In order to analyze the selected in 2007 and2008 1, February, the steam metering point statistical data analysis, see table 1.

          As can be seen, outside plant steam line in 2007 the average heat loss rate of only54.95%,2008 1, February average heat loss rate reached74.85%, causing energy loss is very serious.

          The 2reason analysis

          For outside plant steam line heat loss is serious problem, the following from the steam quality, external insulation, vapor velocity and pipe bracket for heat loss analysis in four aspects.

          2.1steam quality

          From July 10, 2007 to July 14th steam factory parameters are shown in table 2.

          From the data in Table 2can be seen, the factory steam parameters meet the design requirements, so the steam supply quality is not caused by plant steam line heat loss cause.

          2.2external insulation

          Through to the live steam line insulation inspection, overhead vapor line insulation appearance is better, and the underground pipeline insulation loss is more serious, especially from Dushanzi passenger station to the northeast corner of the second steam line, insulation layer off serious, already cannot satisfy the requirements of pipeline insulation. In order to facilitate analysis from May 7, 2008 to May 9th, we selected eight monitoring point on overhead vapor line and underground (with trench ) steam line insulation layer of external temperature were tested and analyzed in this paper. The data in table3.

          According to the people's Republic of China National Standard" heat delivery system for energy saving of" GB / T15910-1995, insulation structure of surface temperature rise should not exceed the table 4 or5provisions to allow the maximum surface temperature rise, table 4, table 5.

          From table 3, table 4 and table 5data contrast can be seen, overhead and underground steam pipe surface temperature exceeds the requirements of the national technical standard, the visible vapour pipeline insulation standards is caused by steam line heat loss serious reason.

          2.3 steam flow rate

          In order to ensure the steam in the process of conveying the heat quality, required a certain steam velocity, known as the economic flow velocity. When the steam flow rate is lower than the economic flow velocity, will increase the steam in the process of conveying the heat loss. Study of plant steam line in the steam in the process of conveying velocity, we focused on plant steam line, in accordance with the steam load20t / h, divided into 8 sections,19steam point to plant different diameter steam line flow and velocity calculations, see Table 6, table 7.

          From table 6, table 7data contrast, as can be seen, according to the maximum operating load calculation, the proximal end of the DN150and DN200diameter steam line can meet the requirements of the economic flow velocity, but the distal end of the DN150, DN300and DN500diameter steam line due to long distance transportation, load gradually reduce and the tube diameter and the steam load mismatch wait for a reason, the steam flow rate is far below the economic flow velocity, is caused by the outside plant steam line of great heat loss is one of the reasons.

          2.4pipe bracket heat loss

          As energy-saving job further, through the application of new high efficient insulation materials, in improving the pipe insulation levels, reducing pipeline heat loss, already gained consensus. But for the pipe bracket heat loss, has not been paid attention to, so, here on the pipe holder heat loss to conduct an analysis. As we know, are present in the steam pipe line pipe support is composed of steel pipe bracket support plate and pipe welding process, plate placed on the frame beam, pipe support heat loss through the support plate and plate is conducting, bottom plate heat radiation ( for steel support plate also has heat ), the process medium heat into the atmosphere, causing the heat loss of steam pipeline.

          關(guān)閉本頁】【返回頁頂

                 Copyright:2012-2018 @ zhongnan handwrar electronic co.,ltd  address: Huizhou City, Guangdong Province Boluo County Long Xizhen Longqiao Boulevard ring Sheng Dong A1 Industrial Park Office telephone: Fax:62988520752-6298851/0752-6298853company website: www.68464.cn  E-mail:hzr@cstcooler.com

          美女超薄透明丝袜美腿| 亚洲乱码少妇中文字幕| 中文字幕亚洲精品乱码在线看| 国产大陆av一区二区三区| 喂奶人妻被中出中文字幕| 特级av一区二区三区| 丁香网五月亚洲丁丁欧美| av黄色精品在线观看| 国产成人欧美一区二区三区在线| 男女性搞视频网站免费| 亚洲国产精品无码久久青草| 亚洲av激情五月性综合| 日韩成人av一区二区| 少妇粗大进出白浆嘿嘿| 人妻少妇邻居少妇好多水在线| 国产精品男人在线播放| 中文字幕一区二区人妻痴汉电车| 亚洲伊人狼人在线视频| 久久久久亚洲AV成人无码电影| 新狼窝色AV性久久久久久| 少妇极品熟妇人妻丰满| 亚洲成人精品免费在线| av永远在线免费观看| 国产精品久久三级精品| 国产不卡一区二区三区视频| 国产东北熟女高潮对白| 亚洲精品无码久久久久APP | 国产精品国产三级国产有见不卡 | 亚洲福利午夜一区二区| 国产一区,二区,三区免费视频| 丰满熟女人妻一区二区| 大又大粗又爽又黄少妇毛片免费| 欧洲亚洲av丰满少妇| 久热精品在线观看视频| 真人裸交一进一出高潮| 久久综合久久国产亚洲| 91成人福利在线观看| 国产综合一区二区三区av | 在线免费观看日韩毛片| 国内精品偷拍视频91| 亚洲免费视频一区二区三区|